Water Level Controller (WLC) GC2200

Water Level Controller (WLC) GC2200

GC2200 Water Level Controller detects water level(s) inside storage tank and/or an elevated tank. The output relay – connected to external mechanical contactor or electronic switch - provides an automatic control to water pump operation. The output relay energizes and the green OUTPUT RELAY LED lights when the water level inside elevated tank is sensed under T2 probe and at the same moment enough water detected inside the storage tank (i.e. water level in storage tank is over S2 probe). The output relay de-energizes and the OUTPUT RELAY LED goes out when elevated tank is full of water (i.e. when GC2200 detects water level is above T1 probe).

GC2200 Water Level Controller detects water level(s) inside storage tank and/or an elevated tank.The output relay – connected to external mechanical contactor or electronic switch - provides an automatic control to water pump operation.

The output relay energizes and the green OUTPUT RELAY LED lights when the water level inside elevated tank is sensed under T2 probe and at the same moment enough water detected inside the storage tank (i.e. water level in storage tank is over S2 probe). The output relay de-energizes and the OUTPUT RELAY LED goes out when elevated tank is full of water (i.e. when GC2200 detects water level is above T1 probe).

The output relay de-energizes timelessly when GC2200 detects only a little water inside the storage tank (i.e. water level stays under S2 probe). The GC2200 units are self powered.

Dimension (mm)




Connection Diagram:









Nominal voltage
Frequency
Distance between GC2200 and probes
Relay type
Burden
Operating temperature
Storage temperature
Relative humidity
Weight
Mounting

220Vac + 20%
50 Hz
≤ 1000 m (with 2.5 sqmm control cable)

SPDT – Contact rating 5A (cosφ = 1), 250 Vac
5VA / 4W (max)
0° C … +50° C
-10° C … +70° C
95% (non condensing)
254 gr
DIN rail 35 x 7.5 mm