Megger VLF Sine Wave 34 kV | PORTABLE VLF SINE WAVE TEST SYSTEM

Megger VLF Sine Wave 34 kV | PORTABLE VLF SINE WAVE TEST SYSTEM

The VLF sine wave 34 kV is a multi-purpose device: it can be used for cable testing, sheath testing, and in combination with the optional step voltage probe ESG NT2, for sheath fault pinpointing.

  • High test capacity of 5 µF
  • Suitable for outdoor use (IP 54)
  • Single-button operation
  • Integrated safety system
  • Reporting
  • Continuous duty cycle
The VLF sine wave 34 kV is a compact, robust and portable VLF sine wave test system for medium voltage cables.

The design, optimized for rapid transportation and quick setup, and the continuous duty cycle are two attributes that qualify the system

as an ideal tool for routine cable testing. For both 0.1 Hz sine wave voltage tests and rectangular or DC voltage tests, the VLF sine wave 34 kV fills the highest demands on the test voltage quality and stability. Moreover, the integrated "breakdown detection" shuts down the test voltage in the event of an excessive charge current and guarantees limited damage to the cable.

Consistent single-button operation combined with a sophisticated operating concept allows a fast and targeted use of the system.



FEATURES


  • Testing without operational interruptions
  • AC testing in compliance with DIN VDE, EN, IEEE
  • Compact, rugged, lightweight, and IP 54 for transportation
  • Sheath testing and sheath fault pin-pointing acc. to IEC 60229
  • Maximises user safety through automatic discharge of the test object and earth loop ground monitoring
  • Breakdown detection and load recognition (R, C)
  • Quick & easy logging, and updates via USB port

Output voltage

VLF sine wave0 … 24 kV RMS / 0 ... 34 kV peak
DC voltage± 0 … 34 kV
VFL rectangular voltage0 … 34 kV
Precision± 1 %
Resolution0.1 kV


Output current

Measuring range0 … 14 mA
Precision± 1 %
Resolution1 μA


General

Frequency range0.01 Hz ... 0.1 Hz
autom. frequency adjustment
Output0.6 μF @ 0,1 Hz at 24 kV RMS
5 μF @ 0,01 Hz at 21 kV RMS
Input voltage100 V … 260 V, 50/60 Hz, 400 VA
Sheath testing0 … 5 kV, 0 … 10 kV DC
Sheath fault pinpointing0 … 5 kV, 0 … 10 kV DC,
Pulse rate 1:3 and 1:4
SafetyEarth loop ground monitoring,
autom. discharging of the test object
Dimensions (W x H x D)520 x 450 x 300 mm
Weight25 kg
Protection classIP 20/IP 54 (operation/transportation)
Operating temperature- 20 °C … + 55 °C
Storage temperature- 25 °C … + 70 °C


Type the keywords in the form